always closed. For this, an output contact with a break contact must be routed. The contact opens whenever
the output signal Alarm suppression becomes active, so that tripping or a switching operation does not
cause an alarm (see the logic in 5.6.5.3 Acquisition of Circuit-Breaker Auxiliary Contacts and Further Informa-
tion for more details).
[loschalt-081210-01.tif, 2, en_US]
Figure 5-48 Circuit-Breaker Tripping Alarm Suppression
Settings
Addr. Parameter C Setting Options Default Setting
Circuit break.
_:101 Circuit break.:Output
time
0.02 s to 1800.00 s 0.10 s
_:105 Circuit break.:Indicat. of
breaking values
•
with trip
•
always
always
Information List
No.
Information Data Class
(Type)
Type
Circuit break.
_:500 Circuit break.:>Ready SPS I
_:501 Circuit break.:>Acquisition blocking SPS I
_:502 Circuit break.:>Reset switch statist. SPS I
_:504 Circuit break.:>Reset AcqBlk&Subst SPS I
_:503 Circuit break.:External health ENS I
_:53 Circuit break.:Health ENS O
_:58 Circuit break.:Position DPC C
_:300 Circuit break.:Trip/open cmd. SPS O
_:301 Circuit break.:Close command SPS O
_:302 Circuit break.:Command active SPS O
_:303 Circuit break.:Definitive trip SPS O
_:304 Circuit break.:Alarm suppression SPS O
_:306 Circuit break.:Op.ct. INS O
_:307 Circuit break.:ΣI Brk. BCR O
_:308 Circuit break.:ΣIA Brk. BCR O
_:309 Circuit break.:ΣIB Brk. BCR O
_:310 Circuit break.:ΣIC Brk. BCR O
_:311 Circuit break.:Break.-current phs A MV O
_:312 Circuit break.:Break.-current phs B MV O
_:313 Circuit break.:Break.-current phs C MV O
_:317 Circuit break.:Break. current 3I0/IN MV O
_:314 Circuit break.:Break. voltage phs A MV O
5.6.5.7
5.6.5.8
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual 245
C53000-G5040-C015-9, Edition 11.2017