Application and Setting Notes
Parameter: Maximum Differential Values of Voltage, Frequency and Angle
•
Default setting (_:5071:122) Max. voltage diff. V2>V1 = 5.0 V
•
Default setting (_:5071:123) Max. voltage diff. V2<V1 = 5.0 V
•
Default setting (_:5071:117) Max. frequency diff. f2>f1 = 0.10 Hz
•
Default setting (_:5071:118) Max. frequency diff. f2<f1 = 0.10 Hz
•
Default setting (_:5071:124) Max. angle diff. α2>α1 = 10
o
•
Default setting (_:5071:125) Max. angle diff. α2<α1 = 10
o
2 parameters are available for the differential values voltage, frequency, and angle. Unbalanced closing ranges
can be set with this, if required.
The permissible differential values must ensure that no protection tripping or damage occurs in the system
owing to compensation processes (circulating current) and power swings after interconnection of the parts of
the power system. The settings must not be configured too closely on the other side so that necessary
closures are not blocked.
Typical differential values are selected in the default setting. Depending on the system, the settings must be
checked and adjusted, if necessary.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:5071:1 Synchrocheck 1:Mode
•
off
•
on
•
test
off
_:5071:101 Synchrocheck 1:Min.
operating limit Vmin
0.300 V to 340.000 V 90.000 V
_:5071:102 Synchrocheck 1:Max.
operat. limit Vmax
0.300 V to 340.000 V 110.000 V
_:5071:110 Synchrocheck
1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞ 30.00 s
_:5071:108 Synchrocheck 1:Direct
close command
•
no
•
yes
no
_:5071:126 Synchrocheck 1:Voltage
adjustment
0.500 to 2.000 1.000
De-en.gized switch.
_:5071:105 Synchrocheck 1:Close
cmd. at V1< & V2>
•
no
•
yes
no
_:5071:106 Synchrocheck 1:Close
cmd. at V1> & V2<
•
no
•
yes
no
_:5071:107 Synchrocheck 1:Close
cmd. at V1< & V2<
•
no
•
yes
no
_:5071:103 Synchrocheck 1:V1, V2
without voltage
0.300 V to 170.000 V 5.000 V
_:5071:104 Synchrocheck 1:V1, V2
with voltage
0.300 V to 340.000 V 80.000 V
_:5071:109 Synchrocheck 1:Supervi-
sion time
0.00 s to 60.00 s 0.10 s
6.4.7.2
6.4.7.3
Control Functions
6.4 Synchronization Function
378 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017