Power-System Data
Overview
The Power-system data are provided with each SIPROTEC 5 device and cannot be deleted. You will find them
in DIGSI under SettingsPower-system data.
Structure of the Power-System Data
The Power-system data contain the block General and the Measuring points of the device. The following
figure shows the structure of the Power-system data:
[dwandata-180912-01.tif, 2, en_US]
Figure 5-1 Structure of the Power-System Data
In order to adjust its functions to the application, the device requires some data about the power system. The
necessary settings can be found in the Power-system data under General as well as in the Measuring points.
i
i
NOTE
You can find information on the supervision-function parameters in chapter 8.3 Supervision of the Secon-
dary System.
Type and scope of the required measuring points depend on the application. Possible measuring points are:
Voltage 3-phase (measuring point V 3-ph)
Current 3-phase (measuring point I 3-ph)
Voltage 1-phase (measuring point V 1-ph)
Current 1-phase (measuring point I 1-ph)
The measuring points have interfaces to the function groups requiring voltage and/or current measured values
of the power system.
Application and Setting Notes – General Settings
Parameter: Phase sequence
Recommended setting value (_:2311:101) Phase sequence= ABC
The parameter Phase sequence is used to set the phase sequence (ABC) or (ACB). The setting value applies
to the entire SIPROTEC 5 device.
Use the General function to set the settings in the power-system data.
You can find detailed information about phase-rotation reversal in chapter 7.23.1 Overview of Functions.
5.1
5.1.1
5.1.2
5.1.3
Function-Group Types
5.1 Power-System Data
182 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017