Addr. Parameter C Setting Options Default Setting
_:18 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:106 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: bin.input
_:34 User curve #:Effected by
binary input
no
yes
no
_:41 User curve #:Stage
blocked
no
yes
no
_:19 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:107 User curve #:Time dial 0.05 to 15.00 1.00
Information List
No.
Information Data Class
(Type)
Type
User curve #
_:81 User curve #:>Block stage SPS I
_:501 User curve #:>Release delay & op. SPS I
_:84 User curve #:>Activ. dyn. settings SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate ACT O
_:62 User curve #:Dyn.set. AR cycle1act. SPS O
_:63 User curve #:Dyn.set. AR cycle2act. SPS O
_:64 User curve #:Dyn.set. AR cycle3act. SPS O
_:65 User curve #:Dyn.set. ARcycl.>3act SPS O
_:66 User curve #:Dyn.set. CLP active SPS O
_:67 User curve #:Dyn.set. BI active SPS O
_:68 User curve #:Dyn. set. blks. pickup SPS O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:309 User curve #:Direction ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O