Addr. Parameter C Setting Options Default Setting
_:4201:104 Control:Check switching
authority
•
no
•
yes
•
advanced
yes
_:4201:105 Control:Check if pos. is
reached
•
no
•
yes
yes
_:4201:106 Control:Check double
activat. blk.
•
no
•
yes
yes
_:4201:107 Control:Check blk. by
protection
•
no
•
yes
yes
Switching authority
_:4201:151 Control:Swi.dev. related
sw.auth.
•
0
•
1
false
_:4201:152 Control:Specific sw.
authorities
•
0
•
1
true
_:4201:115 Control:Specific sw.auth.
valid for
•
station
•
station/remote
•
remote
station/remote
_:4201:153 Control:Num. of specific
sw.auth.
2 to 5 2
_:4201:155 Control:Ident. sw.auth. 1 Freely editable text
_:4201:156 Control:Ident. sw.auth. 2 Freely editable text
_:4201:157 Control:Ident. sw.auth. 3 Freely editable text
_:4201:158 Control:Ident. sw.auth. 4 Freely editable text
_:4201:159 Control:Ident. sw.auth. 5 Freely editable text
_:4201:154 Control:Multiple specific
sw.auth.
•
0
•
1
false
CB test
_:6151:101 CB test:Dead time 0.00 s to 60.00 s 0.10 s
_:6151:102 CB test:Trip only
•
0
•
1
false
_:6151:103 CB test:Consider current
criterion
•
0
•
1
false
_:6151:104 CB test:Current
threshold
1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
Information List
No.
Information Data Class
(Type)
Type
Trip logic
_:5341:300 Trip logic:Trip indication ACT O
Circuit break.
_:4261:500 Circuit break.:>Ready SPS I
_:4261:501 Circuit break.:>Acquisition blocking SPS I
_:4261:502 Circuit break.:>Reset switch statist. SPS I
5.6.9
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
250 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017