Addr. Parameter C Setting Options Default Setting
_:2311:136 General:Op. mode
BFP
•
unbalancing
•
I> query
unbalancing
Trip logic
_:5341:101 Trip logic:Trip at
2ph short circuit
•
3-pole
•
1-pole, leading phase
•
1-pole, lagging phase
3-pole
_:5341:102 Trip logic:3-pole
coupling
•
with pickup
•
with trip
with trip
_:5341:103 Trip logic:Reset of
trip command
•
with I<
•
with I< & aux.contact
•
with dropout
with I<
Circuit break.
_:4261:101 Circuit
break.:Output time
0.02 s to 1800.00 s 0.10 s
_:4261:105 Circuit
break.:Indicat. of
breaking values
•
with trip
•
always
always
Manual close
_:6541:101 Manual
close:Action time
0.01 s to 60.00 s 0.30 s
_:6541:102 Manual close:CB
open dropout delay
0.00 s to 60.00 s 0.00 s
Control
_:4201:101 Control:Control
model
•
status only
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:4201:102 Control:SBO time-
out
0.01 s to 1800.00 s 30.00 s
_:4201:103 Control:Feedback
monitoring time
0.01 s to 1800.00 s 1.00 s
_:4201:104 Control:Check
switching authority
•
no
•
yes
•
advanced
yes
_:4201:105 Control:Check if
pos. is reached
•
no
•
yes
yes
_:4201:106 Control:Check
double activat. blk.
•
no
•
yes
yes
_:4201:107 Control:Check blk.
by protection
•
no
•
yes
yes
Switching authority
_:4201:151 Control:Swi.dev.
related sw.auth.
•
0
•
1
false
_:4201:152 Control:Specific sw.
authorities
•
0
•
1
true
_:4201:115 Control:Specific
sw.auth. valid for
•
station
•
station/remote
•
remote
station/remote
_:4201:153 Control:Num. of
specific sw.auth.
2 to 5 2
Control Functions
6.2 Switching Devices
322 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017