Addr. Parameter C Setting Options Default Setting
_:14011:147 90V V.contr.2w:VT
supervision threshold
0.5 % to 10.0 % 10.0 %
_:14011:148 90V V.contr.2w:VT
supervision time delay
1 s to 600 s 10 s
_:14011:149 90V V.contr.2w:Circul.
current blocking
•
off
•
on
on
_:14011:150 90V V.contr.2w:Circul.
current threshold
10 % to 500 % 50 %
_:14011:151 90V V.contr.2w:Circul.
current time delay
0 s to 1000 s 60 s
Line drop comp.
_:14011:125 90V V.contr.2w:Line
drop compensation
•
off
•
LDC-Z
•
LDC-XandR
off
_:14011:126 90V V.contr.2w:Target
voltage rising
0.0 % to 20.0 % 4.0 %
_:14011:127 90V V.contr.2w:Max
load current
0.0 % to 500.0 % 100.0 %
_:14011:153 90V V.contr.2w:R line 0.00 Ω to 30.00 Ω 0.00 Ω
_:14011:154 90V V.contr.2w:X line -30.00 Ω to 30.00 Ω 0.00 Ω
Limiting
_:14011:102 90V V.contr.2w:Lower
tap-position limit
-128 to 127 1
_:14011:103 90V V.contr.2w:Higher
tap-position limit
-128 to 127 15
_:14011:128 90V V.contr.2w:Vmin
limiting
•
off
•
on
on
_:14011:129 90V V.contr.2w:Vmin
threshold
10.000 V to 340.000 V 105.000 V
_:14011:130 90V V.contr.2w:Vmin
time delay
0 s to 20 s 10 s
_:14011:131 90V V.contr.2w:Vmax
limiting
•
off
•
on
on
_:14011:132 90V V.contr.2w:Vmax
threshold
10.000 V to 340.000 V 115.000 V
_:14011:133 90V V.contr.2w:Vmax
time delay
0 s to 20 s 10 s
Blocking
_:14011:134 90V V.contr.2w:Blocking
behavior
•
Auto
•
Auto-Manual
Auto-Manual
_:14011:135 90V V.contr.2w:V<
Blocking
•
off
•
on
on
_:14011:136 90V V.contr.2w:V<
Threshold
10.000 V to 340.000 V 90.000 V
_:14011:137 90V V.contr.2w:V< Time
delay
0 s to 20 s 0 s
_:14011:138 90V V.contr.2w:I>
Blocking
•
off
•
on
on
_:14011:139 90V V.contr.2w:I>
Threshold
10 % to 500 % 150 %
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 503
C53000-G5040-C015-9, Edition 11.2017