Addr. Parameter C Setting Options Default Setting
_:14011:140 90V V.contr.2w:I> Time
delay
0 s to 20 s 0 s
_:14011:141 90V V.contr.2w:I<
Blocking
off
on
off
_:14011:142 90V V.contr.2w:I<
Threshold
3 % to 100 % 10 %
_:14011:143 90V V.contr.2w:I< Time
delay
0 s to 20 s 10 s
Three-Winding Transformer
Addr. Parameter C Setting Options Default Setting
Winding 1
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:103 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Winding 2
_:2311:102 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:104 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
General
_:15601:1 90V V.contr.3w:Mode
off
on
test
on
_:15601:101 90V V.contr.3w:Oper-
ating mode
Manual
Auto
Manual
_:15601:157 90V V.contr.3w:Winding
selection
Winding 1
Winding 2
WithMaxLoad
Winding 1
_:15601:161 90V V.contr.3w:Winding
selection
Winding 1
Winding 2
Winding 1
Control tap changer
_:15601:107 90V V.contr.3w:Check
switching authority
no
yes
yes
_:15601:109 90V V.contr.3w:Control
model
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
SBO w. enh.
security
_:15601:110 90V V.contr.3w:SBO
time-out
0.01 s to 1800.00 s 30.00 s
_:15601:111 90V V.contr.3w:Feed-
back monitoring time
0.01 s to 1800.00 s 10.00 s
Voltage Control
_:15601:164 90V V.contr.3w:Number
of target voltage
1
2
3
4
1
_:15601:112 90V V.contr.3w:Target
voltage 1 w1
10.000 V to 340.000 V 110.000 V
_:15601:165 90V V.contr.3w:Target
voltage 2 w1
10.000 V to 340.000 V 110.000 V
_:15601:166 90V V.contr.3w:Target
voltage 3 w1
10.000 V to 340.000 V 110.000 V
Control Functions
6.9 Voltage Controller
504 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017