Addr. Parameter C Setting Options Default Setting
_:15601:154 90V V.contr.3w:X line
w1
-30.0 Ω to 30.0 Ω 0.0 Ω
_:15601:155 90V V.contr.3w:R line
w2
0.0 Ω to 30.0 Ω 0.0 Ω
_:15601:156 90V V.contr.3w:X line
w2
-30.0 Ω to 30.0 Ω 0.0 Ω
Limiting
_:15601:102 90V V.contr.3w:Lower
tap-position limit
-128 to 127 1
_:15601:103 90V V.contr.3w:Higher
tap-position limit
-128 to 127 15
_:15601:128 90V V.contr.3w:Vmin
limiting
off
on
on
_:15601:129 90V V.contr.3w:Vmin
threshold w1
10.000 V to 340.000 V 105.000 V
_:15601:148 90V V.contr.3w:Vmin
threshold w2
10.000 V to 340.000 V 105.000 V
_:15601:130 90V V.contr.3w:Vmin
time delay
0 s to 20 s 10 s
_:15601:131 90V V.contr.3w:Vmax
limiting
off
on
on
_:15601:132 90V V.contr.3w:Vmax
threshold w1
10.000 V to 340.000 V 115.000 V
_:15601:149 90V V.contr.3w:Vmax
threshold w2
10.000 V to 340.000 V 115.000 V
_:15601:133 90V V.contr.3w:Vmax
time delay
0 s to 20 s 10 s
Blocking
_:15601:134 90V V.contr.3w:Blocking
behavior
Auto
Auto-Manual
Auto-Manual
_:15601:135 90V V.contr.3w:V<
Blocking
off
on
on
_:15601:136 90V V.contr.3w:V<
Threshold w1
10.000 V to 340.000 V 90.000 V
_:15601:150 90V V.contr.3w:V<
Threshold w2
10.000 V to 340.000 V 90.000 V
_:15601:137 90V V.contr.3w:V< Time
delay
0 s to 20 s 0 s
_:15601:138 90V V.contr.3w:I>
Blocking
off
on
on
_:15601:139 90V V.contr.3w:I>
Threshold
10 % to 500 % 150 %
_:15601:140 90V V.contr.3w:I> Time
delay
0 s to 20 s 0 s
_:15601:141 90V V.contr.3w:I<
Blocking
off
on
off
_:15601:142 90V V.contr.3w:I<
Threshold
3 % to 100 % 10 %
_:15601:143 90V V.contr.3w:I< Time
delay
0 s to 20 s 10 s
Control Functions
6.9 Voltage Controller
506 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017