Addr. Parameter C Setting Options Default Setting
_:781:37 Inverse-T 1:Stage
blocked
no
yes
no
_:781:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:103 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:781:31 Inverse-T 1:Effected by
AR cycle 3
no
yes
no
_:781:38 Inverse-T 1:Stage
blocked
no
yes
no
_:781:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:104 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:781:32 Inverse-T 1:Effected by
AR cycle gr. 3
no
yes
no
_:781:39 Inverse-T 1:Stage
blocked
no
yes
no
_:781:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:105 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: Cold load PU
_:781:33 Inverse-T 1:Effect. b.
cold-load pickup
no
yes
no
_:781:40 Inverse-T 1:Stage
blocked
no
yes
no
_:781:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:781:106 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: bin.input
_:781:34 Inverse-T 1:Effected by
binary input
no
yes
no
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
654 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents