Voltage-transformer connection phase-to-ground: V
act-sec
< 58.7 V
Voltage-transformer connection phase-to-phase: V
act-sec
< 58.7 V ⋅√3 = 101.6 V
•
Check the overcurrent blocking.
NOTE
The overcurrent blocking works with the maximum current of all phases, for this reason, check the phases
A, B, and C separately.
Example
Parameters Value
Power system → CT 3-phase:Rated primary current I
CT-prim
7500 A
Power system → CT 3-phase:Rated secondary current I
CT-sec
1 A
Voltage cont. 2w → General:Rated current I
rated
5500 A
[fo_ibs_overcur_block, 1, en_US]
If you set the parameter I> Threshold to 150 %, this results in an infeed current secondary of I
act-sec
> 1.1 A
for the example.
Line Compensation
•
Check the Z Compensation.
The parameter Target voltage rising represents the voltage drop across the line as a % at rated load. In
case of a voltage drop primary of 504 V across the line at rated current, according to the setting notes in
6.9.4.4 Line Compensation, this results in a setting value of 4.8 %.
The secondary current to be fed in at a load current for the 100 % load case results in:
[fo_ibs_load_current, 1, en_US]
where:
I
CT-prim
Power system → CT 3-phase:Rated primary current
I
CT-sec
Power system → CT 3-phase:Rated secondary current
I
rated
Voltage cont. 2w → General:Rated current
The secondary voltage to be fed in for the 100 % load case with a control deviation D [%] to be tested for the
voltage-transformer connection phase-to-ground results in:
[fo_ibs_sec_volt, 1, en_US]
For the voltage-transformer connection phase-to-phase, the reference must be multiplied with the factor √3.
For a control deviation of D = 0 % to be tested and a setting value Target voltage rising of 4.8 %, in
the example, for voltage-transformer connection phase-to-ground, this results in a secondary infeed voltage
of: