Parameter: Neutr.point in dir.of ref.obj
•
Default setting (_:8881:116) Neutr.point in dir.of ref.obj = yes
The Neutr.point in dir.of ref.obj parameter is used to set the direction of the neutral point of the
current transformer (see following figure). Often, the neutral point of the current transformer is determined
by the direction of the protected object (for example, in the direction of the line, cable, transformer). For this
reason, the default setting of the parameter was defined as yes.
When switching the parameter, the direction of the phase currents and of the ground current IN or IN-sepa-
rate is rotated device-internally.
[dwpolstromwdl-251013, 1, en_US]
Figure 5-3 Polarity of Current Transformers
Parameter: Inverted phases
•
Default setting (_:8881:114) Inverted phases = none
The Inverted phases parameter is intended for special applications, for example, pumped-storage hydro-
power plants (see Chapter Phase-rotation reversal). This default setting may be retained for power-system
protection applications.
Parameter: Magnitude correction
•
Default setting (_:3841:103) Magnitude correction = 1.000
When using the Magnitude correction parameter, you adjust the magnitude (magnitude correction) for
the current input. This allows you to correct the tolerances of the primary current transformer phase-selec-
tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.
NOTE
The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.
You will find more parameters in chapter 8.3.1 Overview.
Note Regarding Routable Data
Indications for the current rotating field can be found in Information routing under Power system →
General in DIGSI 5. The indication
Freq.out of oper.range
means that the frequency operating range
Function-Group Types
5.1 Power-System Data
188 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017