Addr. Parameter C Setting Options Default Setting
_:8881:127 CT 3-phase:Tracking
•
inactive
•
active
active
_:8881:130 CT 3-phase:Measuring-
point ID
0 to 100 0
CT phases
_:8881:101 CT 3-phase:Rated primary
current
1.0 A to 100000.0 A 1000.0 A
_:8881:102 CT 3-phase:Rated secon-
dary current
•
1 A
•
5 A
1 A
_:8881:117 CT 3-phase:Current range
•
1.6 x IR
•
8 x IR
•
20 x IR
•
100 x IR
100 x IR
_:8881:118 CT 3-phase:Internal CT type
•
CT protection
•
CT measurement
CT protection
_:8881:116 CT 3-phase:Neutr.point in
dir.of ref.obj
•
no
•
yes
yes
_:8881:114 CT 3-phase:Inverted phases
•
none
•
AC
•
BC
•
AB
none
_:8881:107 CT 3-phase:CT error
changeover
1.00 to 10.00 1.00
_:8881:108 CT 3-phase:CT error A 0.5 % to 50.0 % 5.0 %
_:8881:109 CT 3-phase:CT error B 0.5 % to 50.0 % 15.0 %
CT IN
_:8881:104 CT 3-phase:Rated primary
current
1.0 A to 100000.0 A 1000.0 A
_:8881:105 CT 3-phase:Rated secon-
dary current
•
1 A
•
5 A
1 A
_:8881:119 CT 3-phase:Current range
•
1.6 x IR
•
8 x IR
•
20 x IR
•
100 x IR
100 x IR
_:8881:120 CT 3-phase:Internal CT type
•
CT protection
•
CT measurement
CT protection
CT IN2
_:8881:106 CT 3-phase:Rated primary
current
1.0 A to 100000.0 A 1000.0 A
_:8881:113 CT 3-phase:Rated secon-
dary current
1 A to 5 A 1 A
_:8881:121 CT 3-phase:Current range
•
1.6 x IR
•
8 x IR
•
20 x IR
•
100 x IR
1.6 x IR
_:8881:122 CT 3-phase:Internal CT type
•
CT protection
•
CT measurement
CT protection
CT 1
_:3841:103 CT 1:Magnitude correction 0.010 to 10.000 1.000
Function-Group Types
5.1 Power-System Data
190 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017