Figure 9-15
Options for Editing the Names of the Individual Phasors
NOTE
You can only rename each individual phasor when you set the parameter Positive-sequence system
only to No in the functional settings. Otherwise you will only be offered one single phasor for each 3-
phase measuring point for renaming.
Routing Binary Signals
You can connect binary inputs or CFC information with binary channels of the PMU via DIGSI information
routing. You will find, in the Phasor Measurement Unit (PMU) folder, the Binary information transmission
function block in the DIGSI function library (see the following figure). You can instantiate this function block
up to 10 times in one PMU function group. Each of these function blocks contains 8 options for routing binary
channels.
Measured Values, Energy Values, and Supervision of the Primary System
9.5 Phasor Measurement Unit (PMU)
1014 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017