A new average value is formed every 10 min at hh:00, hh:10, hh:20, hh:30, hh:40, hh:50. All measured
values obtained during the last 5 min are used to form the average value.
If these settings are changed to 11:03:25, for instance, the average values are first reset and "---" appears in
the display. The 1st average value is then formed at 11:10:00.
Measured Values, Energy Values, and Supervision of the Primary System
9.7 Average Values
SIPROTEC 5, High-Voltage Bay Controller, Manual 1039
C53000-G5040-C015-9, Edition 11.2017