Figure 3-47 Connection via Singlemode Optical Fiber
[dwmultim-070611-05.tif, 1, en_US]
Figure 3-48 Connection via Communication Network with a G703.1 Interface
The connection to the multiplexer is established via a communication converter with a G703.1 interface (64
kBit/s) or X21 interface (64 kBit/s to 512 kBit/s). You can set the bit rate for the KU-XG-512 (for X21), KU-
XG-256 (for X21), KU-XG-128 (for X21), and KU-XG-64 (for X21 or G703.1) with the parameter Connection
via.
You can find more detailed information in Table 3-13.
[dwmultim-070611-06.tif, 1, en_US]
Figure 3-49 Connection via Communication Network with a G703.6 Interface
The connection to the multiplexer is established with 512 kBit/s via a communication converter with a G703.6
interface (E1 with 2 MBit/s or T1 with 1.44 MBit/s). The communication converter offers a 2nd interface for
connecting an additional protection interface.
Make the setting for the bit rate with KU-2M-512 with 512 kBit/s in accordance with Table 3-13 with the
parameter Connection via.
System Functions
3.5 Protection Communication
SIPROTEC 5, High-Voltage Bay Controller, Manual 105