[dwklbsp2-120124-01.tif, 1, en_US]
Figure 9-37 Characteristic Curve of a 20-mA Input (Example 2)
In this example, Range active is selected. The Upper limit is at 15 mA, the Lower limit is at 5 mA
and the Conversion factor remains at 100. The total results in a characteristic curve as shown in the
following figure, taking into account all possible valid measured values from -24 mA to +24 mA. The param-
eter Upper limit - Sensor is the calculated measured value if the input current corresponds to the value
in the Upper limit setting. The parameter Lower limit - Sensor is the calculated measured value if
the input current corresponds to the value in the Lower limit setting.
[dwklges2-120124-01.tif, 2, en_US]
Figure 9-38
Total Characteristic Curve in Example 2
Measured Values, Energy Values, and Supervision of the Primary System
9.12 Measuring Transducers
1052 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017