You can find a short introduction into parameter setting and routing of the binary inputs for the tap position in
chapter 6.8.2 Application and Setting Notes.
Besides the tap-position display via
BCD with prefix
, the SIPROTEC 5 device offers the option to code the
tap position as follows:
Binary
1-of-n
BCD
Table
Gray Code
IEC 61850 GOOSE indication (Type BSC)
Optionally, you can also use an mA signal or a resistance-coded tap-position display. An ANAI module must be
installed for the analog integration of the tap-position signal.
Checking the Tap Position
The active binary input is marked with a cross in the device menu under the entry Binary IO. Siemens recom-
mends driving through all positions of the tap changer completely, if possible, thereby testing the correct tap-
changer position indication once the parameterization of the tap position detection is finished and the tap-
position display is activated.
You can carry out the tap-position check from the on-site operation panel or from the DIGSI Online-Editor. If
you are using the DIGSI Online-Editor, set the switching authority of the device to
Remote
and the operating
mode of the voltage controller to Manual.
[sc_ibs_contr_func, 1, en_US]
Figure 10-10 DIGSI Online-Editor
Functional Tests
10.10 Commissioning Hints for Voltage Control
1078 SIPROTEC 5, High-Voltage Bay Controller, Manual