Priority 2:
Response time, total approx.
For 2 ends Minimum 9 ms
Typical 16 ms
For 3 ends Minimum 12 ms
Typical 18 ms
For 6 ends Minimum 17 ms
Typical 23 ms
Dropout times, total approx.
For 2 ends Typical 24 ms
For 3 ends Typical 25 ms
For 6 ends Typical 32 ms
Priority 3
36
Response time, total approx.
For 2 ends Minimum
Typical 100 ms
For 3 ends Minimum
Typical 150 ms
For 6 ends Minimum
Typical 200 ms
Dropout times, total approx.
For 2 ends Typical 100 ms
For 3 ends Typical 150 ms
For 6 ends Typical 200 ms
36
Times cannot be determined because the signals are transmitted in fragments.
Technical Data
11.2 Protection Interface and Protection Topology
SIPROTEC 5, High-Voltage Bay Controller, Manual 1105
C53000-G5040-C015-9, Edition 11.2017