EasyManua.ls Logo

Siemens 6MD86 - Page 119

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
i
i
NOTE
You can use the following procedure to reset the measured values for the protection interface directly in
the device:
Device functions > x Device protection comm. > Protection interface y > Reset measured values.
Output Signals of the Protection Interface
Each individual protection interface provides the following indications for commissioning and diagnosing
communication:
Indication Description
(_:5161:301) Status
of lay. 1 and 2
The output signal gives you information about the state of communication layers
1 and 2 (1: Physical Layer, 2: Data Link Layer). The following indications values
are possible:
Initialized
:
The protection interface is not connected and is in the Initial state.
Protection interface connected
:
The protection interface is connected to the protection interface of a device.
Protection interface disturbance
:
The protection interface has not received any valid telegrams for the time
set in parameter (_:5161:107) Disturbance alarm after.
Protection interface failure
:
The protection interface has not received any valid telegrams for the time
set in parameter (_:5161:108) Transm. fail. alarm after .
not present
:
The protection interface has not been assigned to a communication
channel.
System Functions
3.5 Protection Communication
SIPROTEC 5, High-Voltage Bay Controller, Manual 119
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals