Channel Type Name Values Description - Diagnostic
Information for Log PI
Protection interfaces - log Build Date/time Date and time of the log
version
Diagnostic Data of the Protection-Interface Log in DIGSI 5
The following figures and tables describe the displays of the protection-interface log.
[scdiamed-140912-01, 1, en_US]
Figure 3-68 Diagnostic Data of the Protection-Interface Log - Media Status
Table 3-19 Description of Diagnostic Data under Media Status
Protection Interfaces - Log
Type
Name Values Description - Media Status
Interface (in Direction of
Outside Interface)
Media Status Baud rate 64 kBit/s; 128 kBit/s; 512
kBit/s; 2048 kBit/s; 30 MBit/s;
<unknown>
HDLC baud rate:
FO: 64 kBit/s to 2048 kBit/s
for 820-Nm USART modules
LDFO: 30 MBit/s for
1300/1500-Nm long-
distance modules
Error case: <unknown>
Media Status LinkState N/A, UP, DOWN FO: N/A (always display N/A)
Media Status TransceiverDetection N/A, NO Transceiver
detected, Transceiver
detected
FO: N/A (always N/A)
(NO Transceiver detected,
Transceiver detected),
Error case: N/A
System Functions
3.5 Protection Communication
SIPROTEC 5, High-Voltage Bay Controller, Manual 123
C53000-G5040-C015-9, Edition 11.2017