example. If you select the General software filter setting, the general settings for software filtering of
spontaneous position changes and for position changes caused by a switching command apply. The settings
for spontaneous position changes can then not be edited. A separate filtering for spontaneous position
changes is activated with the Spontaneous software filter setting and you can edit the settings for
this.
Chatter blocking can be activated or deactivated as a parameter of the position in the Circuit breaker or
Disconnector function block.
[scflatte-180315, 1, en_US]
Figure 3-79
Setting Chatter Blocking
The settings for the chatter blocking function are set centrally for the entire device in DIGSI. They are acces-
sible as settings in the General function group (see the following figure).
[scchattr-180315, 1, en_US]
Figure 3-80 Chatter-Blocking Settings
System Functions
3.8 Other Functions
144 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017