Figure 5-64 Making the Communication Settings
With the selection of the SUP protocol for the 20-mA unit DIGSI automatically adds the function group Analog
units to your device configuration. You can now instantiate the function 20-mA unit serial 1 (see following
figure).
[sc20ser6-220114-01-DE, 1, en_US]
Figure 5-65 Insertion of the Function 20-mA Unit Serial 1
Now, set the channel number over which the SUP protocol runs. In addition, set the slave address of the 20-
mA unit. This address must be set with the same value in the 20-mA unit (refer to the following figure).
For the first use of the 20-mA unit, the following device configuration must be set on the 20-mA unit:
Bus protocol: mod
Device address: 1
Baud rate: 9600
Parity: no
Function-Group Types
5.7 Function-Group Type Analog Units
SIPROTEC 5, High-Voltage Bay Controller, Manual 267
C53000-G5040-C015-9, Edition 11.2017

Table of Contents