Figure 5-84 Making the Communication Settings
With the selection of the SUP protocol for the RTD box DIGSI automatically adds the function group Analog
units to your device configuration. You can now instantiate the function RTD box serial 1 (refer to the
following figure).
[scauser6-190214-01, 1, en_US]
Figure 5-85 Analog-Unit Instance
Now, set the channel number over which the SUP protocol runs. In addition, set the slave address of the RTD
box. This address must be set with the same value in the RTD box (refer to the following figure).
The following device configuration must be set on the TR1200 RTD unit when the RTD unit is used for the first
time:
•
Bus protocol: mod
•
Device address: 1
•
Baud rate: 9600
•
Parity: no
Function-Group Types
5.7 Function-Group Type Analog Units
288 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017