Figure 6-16
Routing in DIGSI
In the previous figure, the switch is connected 1-pole. The protection trip command is routed individually for
the 3 phases (Trip only pole A to Trip only pole C). The protection trip command is routed for the
3 phases (Trip/open cmd. 3-pole). The control will always switch off the 3 poles of the switch. In addi-
tion, the 3 U (Unsaved) allocations of the activation and trip command are set to 3-pole. This routing is also
used by protection functions that trip 3 poles. The close command is issued simultaneously for all 3 phases.
Example: Trip Command during Transition from 1-Pole to 3-Pole
During a transition from 1-pole to 3-pole tripping, Trip only pole A remains active. To inform, for
example, an external AREC whether it is a 1-pole or 3-pole trip, you can use the indications
Trip
logic:Trip indication:1-pole
and
Trip logic:Trip indication:3-pole
.
Control Functions
6.2 Switching Devices
SIPROTEC 5, High-Voltage Bay Controller, Manual 319
C53000-G5040-C015-9, Edition 11.2017