Characteristics Function To Be Found in
Spontaneous position
changes filtered by (Gen.
Software Filt./Spont. Software Filt.)
If the General software
filter setting is selected, the
general settings for software
filtering of spontaneous position
changes and for position changes
caused by a switching command
apply. By selecting Spontaneous
software filter, a separate
filtering is activated for sponta-
neous position changes.
Position of the Control
(1)
function
block
Spontaneous software
filter time
Software filtering time for sponta-
neous position changes
Position of the Control
(1)
function
block
Spontaneous retrigger
filter (yes/no)
Switching on/off retriggering of the
filtering time by spontaneous posi-
tion change
Position of the Control
(1)
function
block
Spontaneous indication
timestamp before filtering
(yes/no)
Consideration of the hardware
filtering time for position-detection
time stamp in case of a sponta-
neous change
Position of the Control
(1)
function
block
Spontaneous suppress
intermediate position
(yes/no)
When activated, only the sponta-
neous change to the intermediate
position is suppressed by the dura-
tion of the software filtering time.
Position of the Control
(1)
function
block
(1) First click Position and then the Details key in the Properties window (below).
Table 6-12 Setting Options of the Controllable Position in the Disconnector Function Block (Chatter
Blocking)
Characteristics Function To Be Found in
Chatter blocking (yes/no) Switching chatter blocking on/off
Position of the Disconnector
(1)
function block
(1) First click Position and then the Details key in the Properties window (below).
Table 6-13 Additional Settings in the Device Settings with effect on the Disconnector
Characteristics Function To Be Found in
Number of permissible
state changes
Chatter-blocking setting value:
Once for the entire device
Device settings (to be found under
Settings)
Chatter test time
Number of chatter tests
Chatter dead time
Chatter test time
The inputs and outputs as well as the setting options of the Disconnector switch function block are described
in the next chapter (see 6.2.3.3 Trigger Variants of the Disconnector). The Control function block is described
identically as the Circuit-breaker function block, with the exception that the command check blocking is avail-
able through protection only with the circuit breaker.
More information on this is can be found in chapter 6.2.2.2 Application and Setting Notes.
Interlocking
The Interlocking function block generates the releases for switchgear interlocking protection. The actual
interlocking conditions are deposited in CFC. For more information on this, see section Chapter
6.3.1 Command Checks and Switchgear Interlocking Protection.
Control Functions
6.2 Switching Devices
328 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017