EasyManua.ls Logo

Siemens 6MD86 - Page 342

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[sc_act additional options sw authority, 3, en_US]
Figure 6-32
Activating Additional Options of the Switching Authority
The additional parameters allow you to set the following options:
Specific sw.auth. valid for (for station/remote, only remote or only station):
With this parameter, you determine for which command source the extended switching-authority check
is used.
Table 6-21
Result Derived from the Combination of the Parameter Value Specific sw.auth. valid
for and the Level of the Command Source (Field Originator/orCat of the Switching
Command)
Command Source
Specific sw.auth. valid for
station station/remote remote
Local, local automatic No check No check No check
Station, station automatic Check Check No check
Remote, remote auto-
matic
No check Check Check
DIGSI No check No check No check
Control Functions
6.3 Control Functionality
342 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals