Figure 6-40
Feeder Bay for a Double Busbar System
The CFC chart that is required to implement the interlocking equation is shown in the next figure.
[scverpla-270511-01.tif, 1, en_US]
Figure 6-41 Interlocking Chart for Bay Interlocking
Since the Disconnector function block provides the defined position On or Off, the exclusive OR gate XOR is
not necessary for interlocking. A simple OR suffices.
Control Functions
6.3 Control Functionality
348 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017