Δf set point for balancing
Smoothing
T close without balancing
Release for the kick pulse
Δf for the kick pulse
Stabilization
Parameter: Balancing frequency f2
Default setting (_:141) Balancing frequency f2 = off
With the parameter Balancing frequency f2, you specify whether you wish to issue balancing
commands for the frequency f2 on the generator side or not.
Parameter Value Description
off
If you select this setting value, no balancing commands are issued for the
frequency f2 on the generator side.
balancing pulses
If you select this setting value, balancing commands are issued for the
frequency f2 on the generator side.
Parameter: T f pulse min
Default setting (_:142) T f pulse min = 0.10 s
With the parameter T f pulse min, you set the minimum time of the control pulse. It corresponds to the
minimum time to which the frequency controller responds. Set the time to this limiting value. The default
setting is a practicable value.
Parameter: T f pulse max
Default setting (_:143) T f pulse max = 1.00 s
With the parameter T f pulse max, you set the maximum time of the control pulse. The default setting is a
practicable value. This allows you to avoid overadjustment of the speed in case of major frequency differ-
ences.
Parameter: df/dt of the controller
Default setting (_:144) df/dt of the controller = 1.00 Hz/s
With the parameter df/dt of the controller, you adjust the balancing commands to the controller.
This allows the set point value to be specified correctly. The control pulse is derived from the measured differ-
ential frequency, the setting value of the parameter df/dt of the controller, and the set point value
Δf set point for balancing. The default setting is a practicable value.
Use the following equation to estimate the duration of the balancing pulse:
[fo_frequency-adujsting-command, 1, en_US]
with:
df
Measured value
Measured differential frequency
Δf set point for
balancing
Parameter for specifying the set point value for the frequency balancing
commands
df/dt of the controller
Parameter for specifying the speed of set point value change
Control Functions
6.4 Synchronization Function
402 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017