The state of the function resulting from the parameter Mode and the superordinate state is shown in the
following table.
Table 2-1 Resulting State of the Function (from Linkage of Parameter Mode and Superordinate State)
Inputs State of the Function
Parameter Mode (of the function) Superordinate State
Off (any) Off
(any) Off Off
On On On
On Test Test
Test On Test
Test Test Test
The following table shows the possible function states:
Table 2-2 Possible States of a Function
Function State Explanation
On The function is activated and operating as defined. The prerequisite is that the health of the
function is OK.
Off The function is turned off. It does not create any information. The health of a disabled func-
tion always has the value OK.
Basic Structure of the Function
2.3 Function Control
SIPROTEC 5, High-Voltage Bay Controller, Manual 41
C53000-G5040-C015-9, Edition 11.2017