[dwswseq1-110913-01.vsd, 1, en_US]
Figure 6-99 Switching Sequence Function Block
Starting and Canceling a Switching Sequence
One of the following methods can be used to start a switching sequence:
On-site operation: menu or display page
Input
>Start
during rising edge, for example, via binary input
Controllable
Start
for the start via a communication protocol, for example, IEC 61850, T103, or DNP
Input
>Start
via a function key
Controllable
Start
via a function key
One of the following methods can be used to cancel a switching sequence:
On-site operation: menu or display page
Input
>Cancel
during rising edge, for example, via binary input
Controllable
Cancel
for the cancelation via a communication protocol, for example, IEC 61850, T103, or
DNP
Input
>Cancel
via a function key
Controllable
Cancel
via a function key
On-Site Operation
If at least one Switching sequence function block is used in the device, a new Switching sequences entry is
shown in the first line of the Control menu. If this menu item is selected, an overview of all switching
sequences and the current status will be displayed (see Figure 6-100, example with 2 switching sequences).
You can start or cancel the switching sequences from this menu.
Control Functions
6.5 Switching Sequences