The indication
Not active
signals that a function is currently not working. The indication
Not active
is
active in the following cases:
Function is disabled
The function is in the health state
Alarm
Function is blocked by an input signal (see Figure 2-3)
All protection-function steps are disabled via the
Enable protection
controllable (state = false). The
indication
Protection inactive
is active.
Blocking of the Operate Indication, No Fault Recording at Pickup
With the Blk. Op. Ind. & Fault Rec. parameter, you define whether a function works as a protection
or a monitoring function. Further, you use this to determine the type and scope of the logging (see following
table)
Parameter Value Description
No
The function works as a protection function. It generates an operate indica-
tion and starts fault recording with pickup. During fault recording, a fault is
created and logged as a fault record in the fault log.
Yes
The function works as a supervision function. The logic runs normally, but
without creating the operate indication. The time-out indication is still
generated and can be processed further if necessary. No fault recording
starts with pickup.
Basic Structure of the Function
2.3 Function Control
SIPROTEC 5, High-Voltage Bay Controller, Manual 43
C53000-G5040-C015-9, Edition 11.2017