[dwregchr-090913-01.vsd, 3, en_US]
Figure 6-129
Control Characteristic with Z Compensation
X and R Compensation (LDC-XandR)
During the application of the X and R compensation, you need the phase data. With this data, it is possible to
precisely compensate the voltage drop of the transmission lines. The following figure shows the effect of this
compensation type.
[dw-line-drop-kompensation-250214-01.vsd, 2, en_US]
Figure 6-130 Phasor Diagram of the X and R Compensation
V
transf
Voltage on the transformer, voltage to be controlled
V
load
Voltage of load point (target voltage, V
load
= V
transf
- V
drop
)
V
drop
Voltage drop of the phase
IR, IX Voltage drop due to R and X of the line