Figure 6-132
Properties Tab of the Parallel Group
You can change this assignment during operation by command, depending on the switching state.
Logic of the Function
[lo_proxy-logic-part_01, 1, en_US]
Figure 6-133 Grouping Logic
Parallel-Control Detection via Group Inputs
You can control up to 8 transformers in parallel in one group or in 4 groups without detecting the system
topology. The devices in parallel operation use exclusively the information transmitted from devices of the
same parallel-control group via GOOSE. The groups of the transformers to be controlled in parallel are set and
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 467
C53000-G5040-C015-9, Edition 11.2017