Figure 6-135
Logic of the Parallel-Control State Detection
Controlling Locally/Remote
The parallel control can be done by setting or via the control. With the parameter setting controllable,
with a CFC block, you can also use a binary input and the status signal of a circuit breaker (Figure 6-138).
First, for the control of the parallel control, set the parameters Parallel mode changeable and Force
master changeable.
You can select one of the 2 options:
•
by setting
•
controllable
[sc_para_oper_change, 1, en_US]
Figure 6-136 Selection for Parallel Control
If you set Parallel mode changeable to controllable, you can read and change the settings for the
parallel control on the device under the following path:
•
Main menu → Commands → Functionality → Voltage cont. 2w1 → Operation
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 469