Additional Parameters for the Three-Winding Transformer and Grid Coupling Transformer: General
Winding 1
Parameter: Rated current
Default setting (_:2311:101) Rated current = 1000.00 A
Parameter: Rated voltage
Default setting (_:2311:103) Rated voltage = 400.00 kV
Winding 2
Parameter: Rated current
Default setting (_:2311:102) Rated current = 1000.00 A
Parameter: Rated voltage
Default setting (_:2311:104) Rated voltage = 400.00 kV
The measured values of the voltage controller can be displayed as primary values, secondary values, or in
percent. With the Rated current and Rated voltage parameters, you set the reference value for the
percentage values.
Tap Changer
The parameters of the tap changer inside the voltage controller correspond to those of the tap changer in
chapter 6.8.2 Application and Setting Notes.
For the tap changer inside the voltage controller, the parameters for the control model are copies of those
from the voltage controller. This concerns the parameters:
Checking the switching authority
Control model
SBO
22
Time-out
Feedback.monitor.time
General
Parameter: Mode
Default setting (_:14011:1) Mode = on
With the Mode parameter, you switch the voltage controller in on, off, or in test operation.
Parameter: Operating mode
Default setting (_:14011:101) Operating mode = Manual
With the Operating mode parameter, you specify whether the controller is operating in Auto mode or in
Manual mode.
Three-Winding Transformer only:
Parameter: Winding selection
Default setting (_:15601:157) Winding selection = Winding 1
With the Winding selection parameter, you specify whether the controller controls the voltage of
Winding 1 or Winding 2. With the WithMaxLoad parameter, the voltage to be controlled is selected
automatically depending on the load current. With this method, you can toggle using the parameter
Winding selection or the controllable
Automatic winding selection
.
If the controllable
Automatic winding selection
is set to Off or is not set, you can influence the
winding to be controlled using the following 2 options:
Using the Winding selection parameter
Using the
Manual winding selection
controllable
The function value
Active winding
shows the winding selection.
22
In the IEC 61850 standard, reservation is known as Select Before Operate (SBO).
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 489