Parameter: Target voltage 2
Default setting (_:14011:157) Target voltage 2 = 110.000 V
With the Target voltage 2 parameter, you specify the 2nd voltage that the voltage controller is supposed
to reach.
Parameter: Target voltage 3
Default setting (_:14011:158) Target voltage 3 = 110.000 V
With the Target voltage 3 parameter, you specify the 3rd voltage that the voltage controller is supposed
to reach.
Parameter: Target voltage 4
Default setting (_:14011:159) Target voltage 4 = 110.000 V
With the Target voltage 4 parameter, you specify the 4th voltage that the voltage controller is supposed
to reach.
Three-Winding Transformer only:
Parameter: Number of target voltage
Default setting (_:15601:164) Number of target voltage = 1
With this parameter, you specify the number of available target voltages (1 W1/2 to 4 W1/2). You can
select a target voltage from the available ones using the function key, communication, or binary input.
Note:
Keep in mind that the parameter Number of target voltage cannot be influenced by way of the
settings group switching.
You can specify the target voltages (1 W1/2 to 4 W1/2) in primary, secondary, or in percent.
For the activation of the target voltage 1 to 4 via a binary input, you need a CFC chart.
Parameter: Target voltage 1 w1
Default setting (_:15601:112) Target voltage 1 w1 = 110.000 V
Parameter: Target voltage 1 w2
Default setting (_:15601:146) Target voltage 1 w2 = 110.000 V
Parameter: Target voltage 2 w1
Default setting (_:15601:165) Target voltage 2 w1 = 110.000 V
Parameter: Target voltage 2 w2
Default setting (_:15601:168) Target voltage 2 w2 = 110.000 V
Parameter: Target voltage 3 w1
Default setting (_:15601:166) Target voltage 3 w1 = 110.000 V
Parameter: Target voltage 3 w2
Default setting (_:15601:169) Target voltage 3 w2 = 110.000 V
Parameter: Target voltage 4 w1
Default setting (_:15601:167) Target voltage 4 w1 = 110.000 V
Parameter: Target voltage 4 w2
Default setting (_:15601:170) Target voltage 4 w2 = 110.000 V
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 491
C53000-G5040-C015-9, Edition 11.2017