Figure 7-3 Internal Start of the 3-Pole Circuit-Breaker Failure Protection Function
[lointsta-160611-01.tif, 3, en_US]
Figure 7-4
Internal Start of the 1/3-Pole Circuit-Breaker Failure Protection Function
External Start
The parameter Start via binary input is used to set whether the external start is initiated by a 1-
channel or 2-channel signal. The required routing of the input signals is compared with the setting. If a
routing is missing, an error message is generated. The Health signal changes to the state
Warning
.
Protection and Automation Functions
7.1 Circuit-Breaker Failure Protection
518 SIPROTEC 5, High-Voltage Bay Controller, Manual