Addr. Parameter C Setting Options Default Setting
_:6601:102 General:CB ready check
bef. start
•
no
•
yes
no
_:6601:103 General:Reclai. time
aft.succ.cyc.
0.50 s to 300.00 s 3.00 s
_:6601:104 General:Block. time aft.
man.close
0.00 s to 300.00 s 1.00 s
_:6601:105 General:Start signal
supervis.time
0.01 s to 300.00 s 0.13 s
_:6601:106 General:CB ready superv.
time
0.01 s to 300.00 s 3.00 s
_:6601:107 General:3-pole operate
by 79
•
no
•
yes
yes
_:6601:108 General:Evolving-fault
detection
•
with trip
•
with pickup
with trip
_:6601:109 General:Response to
evolv. faults
•
strt. evol.flt.dead time
•
blocks 79
blocks 79
_:6601:110 General:Max. dead-time
delay
0.01 s to 300.00 s 0.50 s
_:6601:111 General:Max. dead-time
extension
0.00 s to 300.00 s; ∞ 1.20 s
_:6601:112 General:Send delay f.
remot. close
0.00 s to 300.00 s; ∞ ∞
DLC, RDT
_:6601:113 General:Dead-line check/
reduc.d.t
•
without
•
Reduced dead t. RDT
•
Dead-line check DLC
without
_:6601:114 General:Voltage supervi-
sion time
0.10 s to 30.00 s 0.10 s
_:6601:115 General:Volt. thres.f. live
line/bus
0.300 V to 340.000 V 48.000 V
_:6601:116 General:Volt.thres. f.
dead line/bus
0.300 V to 340.000 V 30.000 V
Cycle 1
_:6571:102 Cycle 1:Start from idle
state allow.
•
no
•
yes
yes
_:6571:103 Cycle 1:Action time 0.00 s to 300.00 s; ∞ 0.20 s
_:6571:108 Cycle 1:Dead time aft. 3-
pole trip
0.00 s to 1800.00 s; ∞ 0.50 s
_:6571:107 Cycle 1:Dead time aft. 1-
pole trip
0.00 s to 1800.00 s; ∞ 1.20 s
_:6571:104 Cycle 1:Dead time aft.
1ph. pickup
0.00 s to 1800.00 s; ∞ 1.20 s
_:6571:105 Cycle 1:Dead time aft.
2ph. pickup
0.00 s to 1800.00 s; ∞ 1.20 s
_:6571:106 Cycle 1:Dead time aft.
3ph. pickup
0.00 s to 1800.00 s; ∞ 0.50 s
_:6571:109 Cycle 1:Dead time aft.
evolv. fault
0.01 s to 1800.00 s 1.20 s
_:6571:111 Cycle 1:CB ready check
bef.close
•
no
•
yes
no
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 577
C53000-G5040-C015-9, Edition 11.2017