Addr. Parameter C Setting Options Default Setting
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:113 User curve #:Threshold
(absolute)
1 A @ 100 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 100 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.000 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.000 A
_:111 User curve #:Pickup
delay
0.00 s to 60.00 s 0.00 s
_:110 User curve #:Reset
instantaneous
disk emulation
disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
_:115 User curve #:Additional
time delay
0.00 s to 60.00 s 0.00 s
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by
AR off/n.ready
no
yes
no
_:35 User curve #:Stage
blocked
no
yes
no
Dyn.set: AR cycle 1
_:29 User curve #:Effected by
AR cycle 1
no
yes
no
_:36 User curve #:Stage
blocked
no
yes
no
_:14 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:102 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by
AR cycle 2
no
yes
no
_:37 User curve #:Stage
blocked
no
yes
no
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Protection and Automation Functions
7.4 Overcurrent Protection, Phases
626 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017