example, signal function x) becomes active and is to take effect, these settings become dynamic, that is,
instantly active. This means that the setting assigned to the signal replaces the standard setting. If the signal
becomes inactive, the standard settings apply again. The activation of the dynamic settings is reported.
Where several signals are active in parallel, the priority specified above shall apply. This means that a signal
with priority 2 precedes that of priority 3. The settings assigned to signal 2 become active.
The functionality of the dynamic settings can be disabled. In this case, the settings assigned to the signals are
not visible and are without effect.
Link to the Device-Internal Function
Automatic Reclosing (Advanced Stage)
[loocp3awe-040311-01, 1, en_US]
Figure 7-73
Influence of the AREC Signals on the Overcurrent-Protection Stage
Protection and Automation Functions
7.4 Overcurrent Protection, Phases