Addr. Parameter C Setting Options Default Setting
General
_:8341:1 Inverse-T 1:Mode
•
off
•
on
•
test
off
_:8341:2 Inverse-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:8341:111 Inverse-T 1:Directional
mode
•
forward
•
reverse
forward
_:8341:11 Inverse-T 1:1-pole
operate allowed
•
no
•
yes
no
_:8341:8 Inverse-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:8341:113 Inverse-T 1:Non-direc-
tional pickup
•
no
•
at volt.< & mem.empty
at volt.< &
mem.empty
_:8341:110 Inverse-T 1:Directional
comparison
•
no
•
yes
no
_:8341:112 Inverse-T 1:Release via
input signal
•
no
•
yes
no
_:8341:10 Inverse-T 1:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:8341:26 Inverse-T 1:Dynamic
settings
•
no
•
yes
no
_:8341:27 Inverse-T 1:Blk. w. inrush
curr. detect.
•
no
•
yes
no
_:8341:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:130 Inverse-T 1:Type of char-
acter. curve
_:8341:114 Inverse-T 1:Min. time of
the curve
0.00 s to 1.00 s 0.00 s
_:8341:131 Inverse-T 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:8341:101 Inverse-T 1:Time dial 0.05 to 15.00 1.00
_:8341:115 Inverse-T 1:Additional
time delay
0.00 s to 60.00 s 0.00 s
Dyn.s: AR off/n.rdy
_:8341:28 Inverse-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:8341:35 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:8341:29 Inverse-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:8341:36 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
686 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017