You can use the Blk. by meas.-volt. failure parameter to control the response of the stage when a
measuring-voltage failure is detected.
A measuring-voltage failure can only be detected if one of the following 2 conditions is met:
•
The device-internal Measuring-voltage failure detection function is configured and switched on.
•
The binary input signal
>Open
of the function block Voltage-transformer circuit breaker is connected to
the voltage-transformer circuit breaker.
Parameter Value Description
yes
The directional overcurrent-protection stage is blocked when a measuring-
voltage failure is detected. Siemens recommends using the default setting,
as correct direction determination cannot be guaranteed if a measuring-
voltage failure occurs.
no
The directional overcurrent-protection stage is not blocked when a meas-
uring-voltage failure is detected.
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 709