Addr. Parameter C Setting Options Default Setting
_:4861:8 Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:4861:104 Definite-T 1:Directional
comparison
•
no
•
yes
no
_:4861:106 Definite-T 1:Release via
input signal
•
no
•
yes
no
_:4861:10 Definite-T 1:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:4861:26 Definite-T 1:Dynamic
settings
•
no
•
yes
no
_:4861:27 Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:4861:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:4 Definite-T 1:Dropout
ratio
0.90 to 0.99 0.95
_:4861:101 Definite-T 1:Dropout
delay
0.00 s to 60.00 s 0.00 s
_:4861:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR off/n.rdy
_:4861:28 Definite-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:4861:35 Definite-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:4861:29 Definite-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:4861:36 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:20 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 2
_:4861:30 Definite-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:4861:37 Definite-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
716 SIPROTEC 5, High-Voltage Bay Controller, Manual