EasyManua.ls Logo

Siemens 6MD86 - Page 720

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Logic of the Advanced Stage
[lodiinva-280812-02.tif, 2, en_US]
Figure 7-113
Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Advanced
Measurand (Basic and Advanced Stage)
The function uses the zero-sequence current (3I0) as a criterion for the ground fault.
Depending on the parameter setting connection type of the Measuring point I-3ph, the zero-sequence
current is measured or calculated. Depending on the applied CT terminal type, the 3I0 Threshold range
varies according to the following table.
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
720 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals