EasyManua.ls Logo

Siemens 6MD86 - Page 790

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pickup Mode
With the Pickup mode parameter, you define whether the protection stage picks up if all 3 measuring
elements detect the overvoltage condition ( 3 out of 3 ) or if only 1 measuring element detects the over-
voltage condition ( 1 out of 3 ).
Measured Value
Use the Measured value parameter to define whether the stage analyzes the phase-to-phase voltages V
AB
,
V
BC
, and V
CA
, or the phase-to-ground voltages V
A
, V
B
, and V
C
.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Pickup and Operate Curve
When the input voltage exceeds the threshold value by a settable value Pickup factor , the stage picks up
and the inverse-time characteristic curve is processed. Operate delay starts. The operate delay is the sum of
inverse-time delay and additional time delay.
Where
T
op
Operate delay
T
inv
Inverse-time delay
T
add
Additional time delay (parameter Additional time delay )
After pickup, the time value T
inv
is calculated for every input voltage that exceeds the threshold. An integrator
accumulates the value 1/T
inv
. Once the accumulated integral reaches the fixed value 1, the inverse-time delay
expires. The additional time delay T
add
starts. The stage operates after the additional time delay expires.
The inverse-time characteristic is shown in the following figure.
[dwovpinv, 2, en_US]
Figure 7-143
Operate Curve of Inverse-Time Characteristic
The inverse-time delay is calculated with the following formula:
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
790 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals