No. Information Data Class
(Type)
Type
_:501 49 Th.overl. #:>Reset thermal replica SPS I
_:502 49 Th.overl. #:>Emergency start SPS I
_:54 49 Th.overl. #:Inactive SPS O
_:52 49 Th.overl. #:Behavior ENS O
_:53 49 Th.overl. #:Health ENS O
_:301 49 Th.overl. #:Current warning SPS O
_:302 49 Th.overl. #:Thermal warning SPS O
_:303 49 Th.overl. #:Block close SPS O
_:55 49 Th.overl. #:Pickup ACD O
_:300 49 Th.overl. #:Operate alarm only ACT O
_:57 49 Th.overl. #:Operate ACT O
_:304 49 Th.overl. #:Time until close MV O
_:305 49 Th.overl. #:Time until trip MV O
_:306 49 Th.overl. #:Overload phase A MV O
_:307 49 Th.overl. #:Overload phase B MV O
_:308 49 Th.overl. #:Overload phase C MV O
_:309 49 Th.overl. #:Overload maximum MV O
_:310 49 Th.overl. #:Equival. current phs A MV O
_:311 49 Th.overl. #:Equival. current phs B MV O
_:312 49 Th.overl. #:Equival. current phs C MV O
_:313 49 Th.overl. #:Equival. current max. MV O
Protection and Automation Functions
7.26 Thermal Overload Protection, 3-Phase - Advanced
SIPROTEC 5, High-Voltage Bay Controller, Manual 891
C53000-G5040-C015-9, Edition 11.2017