Addr. Parameter C Setting Options Default Setting
_:11110:1 Point 10:Mode
off
on
test
off
_:11110:40 Point 10:Threshold stage 1 -50°C to 250°C 100°C
_:11110:41 Point 10:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11110:42 Point 10:Threshold stage 2 -50°C to 250°C 120°C
_:11110:43 Point 10:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11110:44 Point 10:Sensor Setting options depend on config-
uration
Point 11
_:11111:46 Point 11:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
_:11111:1 Point 11:Mode
off
on
test
off
_:11111:40 Point 11:Threshold stage 1 -50°C to 250°C 100°C
_:11111:41 Point 11:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11111:42 Point 11:Threshold stage 2 -50°C to 250°C 120°C
_:11111:43 Point 11:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11111:44 Point 11:Sensor Setting options depend on config-
uration
Point 12
_:11112:46 Point 12:Sensor location
Oil
Ambient
Turn
Bearing
Other
Other
_:11112:1 Point 12:Mode
off
on
test
off
_:11112:40 Point 12:Threshold stage 1 -50°C to 250°C 100°C
_:11112:41 Point 12:Operate delay of
stage 1
0 s to 60 s; ∞ 5 s
_:11112:42 Point 12:Threshold stage 2 -50°C to 250°C 120°C
_:11112:43 Point 12:Operate delay of
stage 2
0 s to 60 s; ∞ 0 s
_:11112:44 Point 12:Sensor Setting options depend on config-
uration
Protection and Automation Functions
7.28 Temperature Supervision
908 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017