Indication Type Group
Warning
Explanation
(_:320) Auxiliary Power Fail SPS Fixed Fault with the auxiliary power supply:
Check the external power supply.
(_:305) Battery failure SPS Battery fault:
Replace the device battery.
To avoid data losses, Siemens recom-
mends replacing the device battery
when the supply voltage of the device is
switched on.
(_:312) Compensation error x ENS Calibration error in module x:
Contact the Customer Support Center.
Quality: Measured values are marked
with the quality attribute of
question-
able
(measured value display with ≈).
(_:314) Offset error x ENS Offset error on module x:
If this indication persists after the device
start, contact the Customer Support
Center.
Quality: Measured values are marked
with the quality attribute of
question-
able
(measured value display with ≈).
(_:306) Clock fail SPS Internal time failure
Check the time settings first.
Then replace the device battery.
If the fault is not remedied, contact
the Customer Support Center.
Quality: The internal time is marked
with the quality attribute of
Clock
Failure
.
(_:319) Error memory SPS Checksum (CRC) error in monitored
memory areas of the device
Measuring-transducer error (x) ENS Hardware error on the measuring-trans-
ducer module on plug-in module posi-
tion E/F/M/N/P:
Contact the Customer Support Center.
Handling an alarm:
(_:504) >Group Warning SPS Fixed Input signal for user-defined generation
of group warning
Time sync.:
(_:305) Time sync. error
SPS Fixed Time synchronization error, the timing
master is faulty:
Check the external time source
first.
Check the external connections.
If the fault is not remedied, contact
the Customer Support Center.
Quality: The internal time is marked
with the quality attribute of
Clock not
synchronized
.
Power-system data:meas. point I-3ph:superv.
bal. I:
(_:71) Failure
SPS CFC
Failure of the current balance (see chap.
8.3.8.1 Overview of Functions )
Supervision Functions
8.8 Error Responses and Corrective Measures
986 SIPROTEC 5, High-Voltage Bay Controller, Manual