B.3 Parameter Table
480 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
F7: Communication Option Card (SI-EM3 and SI-EN3)
F7-01 through F7-42 are common settings used for Modbus TCP/IP, and Ethernet/IP option cards. Other parameters in
the F7 group are used for communication protocol specific settings.
For more details on a specific option
card, refer to the instruction manual for the option card.
No.(Addr.) Name Description Setting Page
F7-01
(3E5H)
<44> <45>
<46>
IP Address 1
Sets the static/fixed IP address.
Parameter F7-01 sets the most significant octet.
Default: 192
Min: 0
Max: 255
F7-02
(3E6H)
<44> <45>
<46>
IP Address 2
Sets the static/fixed IP address.
Parameter F7-02 sets the second most significant octet.
Default: 168
Min: 0
Max: 255
F7-03
(3E7H)
<44> <45>
<46>
IP Address 3
Sets the static/fixed IP address.
Parameter F7-03 sets the third most significant octet.
Default: 1
Min: 0
Max: 255
F7-04
(3E8H)
<44> <45>
<46>
IP Address 4
Sets the static/fixed IP address.
Parameter F7-04 sets the fourth most significant octet.
Default: 20
Min: 0
Max: 255
F7-05
(3E9H)
<46>
Subnet Mask 1
Sets the static/fixed Subnet Mask.
Parameter F7-05 sets the most significant octet.
Default: 255
Min: 0
Max: 255
F7-06
(3EAH)
<46>
Subnet Mask 2
Sets the static/fixed Subnet Mask.
Parameter F7-06 sets the second most significant octet.
Default: 255
Min: 0
Max: 255
F7-07
(3EBH)
<46>
Subnet Mask 3
Sets the static/fixed Subnet Mask.
Parameter F7-07 sets the third most significant octet.
Default: 255
Min: 0
Max: 255
F7-08
(3ECH)
<46>
Subnet Mask 4
Sets the static/fixed Subnet Mask.
Parameter F7-08 sets the fourth most significant octet.
Default: 0
Min: 0
Max: 255
F7-09
(3EDH)
<46>
Gateway Address 1
Sets the static/fixed Gateway address.
Parameter F7-09 sets the most significant octet.
Default: 192
Min: 0
Max: 255
F7-10
(3EEH)
<46>
Gateway Address 2
Sets the static/fixed Gateway address.
Parameter F7-10 sets the second most significant octet.
Default: 168
Min: 0
Max: 255
F7-11
(3EFH)
<46>
Gateway Address 3
Sets the static/fixed Gateway address.
Parameter F7-11 sets the third most significant octet.
Default: 1
Min: 0
Max: 255
F7-12
(3F0H)
<46>
Gateway Address 4
Sets the static/fixed Gateway address.
Parameter F7-12 sets the fourth most significant octet.
Default: 1
Min: 0
Max: 255
F7-13
(3F1H)
Address Mode at Startup
Selects how the option address is set.
0: Static <45>
1: BOOTP
2: DHCP
Default: 2
Min: 0
Max: 2
F7-14
(3F2H)
Duplex Mode Selection
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half duplex forced (port 1)/Auto-negotiate duplex mode and communication speed (port 2)
4: Half duplex forced (port 1)/Full duplex forced (port 2)
5: Auto-negotiate duplex mode and communication speed (port 1)/Half duplex forced (port 2)
6: Auto-negotiate duplex mode and communication speed (port 1)/Full duplex forced (port 2)
7: Full duplex forced (port 1)/Half duplex forced (port 2)
8: Full duplex forced (port 1)/Auto-negotiate duplex mode and communication speed (port 2)
Default: 1
Min: 0
Max: 8
F7-15
(3F3H)
<47>
Communication Speed Selection
Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
101: 10 Mbps (port 1)/100 Mbps (port 2)
102: 100 Mbps (port 1)/10 Mbps (port 2)
Default: 10
Min: 10
Max: 102
F7-16
(3F4H)
Communication Loss Time Out
Sets the time-out value for communication loss detection in tenths of a second. A value of 0
disables the connection time-out.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0.0 s
Min: 0.0 s
Max: 30.0 s
233
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes

Table of Contents

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20